[DNP Slave
Analog

Inputs]

This section is used to override the default values of the class and

deadband assignments for the analog input points.

# Point# Class Deadband

START

This string signals the start of the point definition list.

6 1 2000 #points 0-5=class 1, deadband = 1000

7 1 2000

8 2 1000

END

This string signals the end of the point definition list.

Variable

Name

Description

[DNP Slave

Float Inputs]

This section is used to override the default values of the class and

deadband assignments for the float input points.

# Point# Class Deadband

START

This string signals the start of the point definition list.

0 1 100.

1 2 12.34

2 3 1.23

END

This string signals the end of the point definition list.

Variable

Name

Description

[DNP Slave
Double

Inputs]

This section is used to override the default values of the class and

deadband assignments for the double input points.

# Point# Class Deadband

START

This string signals the start of the point definition list.

0 1 100.

1 2 987.34

2 3 789.23

END

This string signals the end of the point definition list.