ProSoft Technology MVI94-DNP User Manual

Page 82

Advertising
background image

Reference

MVI94-DNP ♦ Flex I/O

User Manual

DNP 3.0 Server over Ethernet Communication Module

Page 82 of 131

ProSoft Technology, Inc.

December 17, 2010

6 Next the ladder logic examines the value of the write_block_code and

determines the data type and offset into the data type data table where the

data will be sourced.

7 The required six-word, write data is copied to the module’s output image

(words 1 to 6). To "trigger" the transfer operation, the ladder logic moves the

write_block_code into word 0 of the output image.

8 The module’s program recognizes the new write_block_code. It transfers the

data to the correct offset in the database using the block number provided.

9 The module sets the last_write_block_code to the value of write_block_code.
10 The module now selects the next read and write blocks. The data for the

processor read operation is placed in the input image and the

write_block_code is set in word 1. The module "triggers" the transfer

operation by setting the new read_block_code in word 0 of the input image.

11 The sequence continues at step 3.
The previous discussion is for normal data transfer operation. The following table

lists the block identification codes used by the module for data transfer.

Data Type

Start Block #

Max Block #

Max # Of Points

Type

Digital Input

0

9

960

Slave

Digital Output

20

29

960

Counters

40

49

30

Analog Input

60

79

120

Float Input

300

319

60

Double Input

320

349

30

Analog Output

80

89

60

Float Output

400

419

60

Double Output

420

449

30

IED Digital Input

100

109

960

Master

IED Digital Output

120

129

960

IED Counters

140

149

30

IED Analog Input

160

179

120

IED Analog Output

180

189

60

Data is transferred between the processor and the module using the block

identification codes of 0 to 189, 300 to 349 and 400 to 449. Other block codes

control the module from the processor’s ladder logic. They are implemented

when the ladder logic needs to control the module. In order to use one of the

blocks, the ladder logic inserts the data and code in the output image of the

module. The data should be set before the code is placed in the block. This

operation should be performed after the receipt of a new write block from the

module.