ProSoft Technology MVI94-DNP User Manual

Page 97

Advertising
background image

MVI94-DNP ♦ Flex I/O

Reference

DNP 3.0 Server over Ethernet Communication Module

User Manual

ProSoft Technology, Inc.

Page 97 of 131

December 17, 2010

Variable
Name

Data
Range

Description

IF Error

Config.
Value

Double Class: 0 to 3

This parameter sets the default class
assignment for points in the double input

dataset. All points not specified in the

override section of the configuration will be
assigned to this class. For class 0, no

events will be generated for the points.

0

AI Deadband: 0 to 32767 This value sets the global deadband for all

analog input points not specified in the

override section. Events will be generated
when the last saved value exceeds the limit

of this parameter.

32767

Float

Deadband:

Any valid

floating-

point value

This value sets the global deadband for all

float input points not specified in the

override section. Events will be generated
when the last saved value exceeds the limit

of this parameter.

0

Double

Deadband:

Any valid

double

floating-
point value

This value sets the global deadband for all

double input points not specified in the

override section. Events will be generated
when the last saved value exceeds the limit

of this parameter.

0

Select/Operat

e Arm Time:

1 to 65535 Time period after select command received

in which operate command will be

performed. After the select command is
received, the operate command will only be

honored if it arrives within this period of

time.

2000

Write Time

Interval:

0 to 1440

minutes

Time interval to set the need time IIN bit

(0=never), which will cause the master to
write the time. Stored in milliseconds in the

module memory.

1440

Data Link

Confirm
Mode:

N, S or A

IED can request acknowledgement from

master station when sending data. The
codes are as follows: N=Never,

S=Sometimes, A=Always

N

Data Link

Confirm Tout:

1 to 65535 Time period to wait for Master Data Link

confirmation of last frame sent. This time is

in milliseconds. This parameter is only used
if the frame is sent with confirmation

requested.

1

Data Link Max

Retry:

0 to 255

Maximum number of retries at the Data Link

level to obtain a confirmation. If this value is

set to 0, retries are disabled at the data link
level of the protocol. This parameter is only

used if the frame is sent with confirmation

requested.

255

App Layer

Confirm Tout:

1 to 65535 Event data contained in the last response

may be sent again if not confirmed within
the millisecond time period set. If

application layer confirms are used with

data link confirms, ensure that the

application layer confirm timeout is set long
enough.

2000

Advertising