[DNP Master

Commands]

This section header defines the location of the DNP master

command list.

START

This string signals the start of the command list.

# 1 2 3 4 5 6 7 8 9 10

#Flags/ Node Data Data Cmd Device Point DNP DB IED DB Poll

#Enable Address Object Variation Func Address Count Address Address

#Interval

6 2 1 0 1 0 -20 -1 0 0

END

This string signals the end of the command list.

Master Port DNP Slave Configuration Values (DNP Master Slave List)

Column

Variable
Name

Data Range

Description

IF Error

Config.
Value

1

DNP
Slave

Address

0 to 65534

This is the slave address for the

unit to override the default values.

Ignore

2

Data Link
Confirm

Mode

Coded Value
(0=Never,

1=Sometimes,

2=Always)

This value specifies if data link
frames sent to the remote device

require a data link confirm. This
value should always be set to zero

for almost all applications.

0

3

Data Link
Confirm

Time-out

1 to 65535

milliseconds

This parameter specifies the time
to wait for a data link confirm from

the remote device before a retry is

attempted.

300

4

Maximum
Retries

for Data
Link

Confirm

0 to 255 retries Maximum number of retries at the

Data Link level to obtain a

confirmation. If this value is set to
0, retries are disabled at the data

link level of the protocol. This

parameter is only used if the

frame is sent with confirmation

requested.

3

5

Applicatio
n Layer

Response

Time-out

1 to 65535

milliseconds

Time-out period the master will
wait for each response message

fragment. If data link confirms are

enabled, make sure the time-out

period is set long enough to

permit all data confirm retries.

5000