ProSoft Technology MVI94-DNP User Manual
Page 32

Configuration
MVI94-DNP ♦ Flex I/O
User Manual
DNP 3.0 Server over Ethernet Communication Module
Page 32 of 131
ProSoft Technology, Inc.
December 17, 2010
Point Count
This parameter defines the number of points in the IED unit. Refer to the
discussion above for the interpretation of this parameter’s values for the different
object types.
DNP DB Address
This parameter defines the starting location in the DNP database for the
command. If the parameter has a value of -1, the DNP database is not used with
the point.
IED DB Address
This parameter defines the starting location in the IED database for the
command. If the parameter has a value of -1, the IED database is not used with
the point.
Poll Interval
This parameter specifies the minimum frequency at which the module should
execute the command. The value is entered in units of seconds. For example, to
execute a command every 10 seconds, enter a value of 10 in the field. A value of
0 for the parameter implies that the command should be executed every scan of
the list.