5.4.5 IIN Bits

MVI94-DNP Module Internal Indication Bits (IIN Bits) for DNP Slave Port
The internal indication bits are stored in a word that follows the function code in

all response messages. These bits report status and error information to the

master DNP device. Below is a description of the word:

First Byte

Bit

Description

0

All stations message received. Set when a request is received with the destination address
set to 0xffff. Cleared after next response. Used to let master station know broadcast

received.

1

Class 1 data available. Set when class 1 data is ready to be sent from the slave to the

master. Master should request class 1 data when this bit is set.

2

Class 2 data available. Set when class 2 data is ready to be sent from the slave to the

master. Master should request class 2 data when this bit is set.

3

Class 3 data available. Set when class 3 data is ready to be sent from the slave to the

master. Master should request class 3 data when this bit is set.

4

Time synchronization required from master. The master should write the date and time when

this bit is set. After receiving the write command the bit will be cleared.

5

Slave digital outputs are in local control. This bit is not used in this application.

6

Not used.

7

Device restart. This bit is set when the slave either warm or cold boots. It is cleared after a

master writes a 0 to the bit.

Second Byte

Bit

Description

0

Bad function code. The function code contained in the master request is not supported for

the specified object/variation.

1

Requested object(s) unknown. Object requested by master is not supported by the

application.

2

Parameters in the qualifier, range or data fields are not valid or out of range for the slave.

3

Event buffer(s) or other application buffers have overflowed. This bit is also set if the slave

receives a multi-frame message from the master.

4

Request understood but requested operation is already executing. The slave will never set

this bit.

5

Bad configuration. The slave configuration is invalid and should be re-configured. If the
configuration is invalid, the slave will set the invalid parameters to default values and

continue to run. Check error log using debug port.

6

Reserved, always 0.

7

Reserved, always 0.