4.7.2 Command Error Codes

Command error codes are generated by the module's program. These errors are

generated when an error occurs when issuing a request or processing a

response of a command list function. The following tables list the command error

codes used in the module:

General Command Errors

Error Code Name

Description

1

Device not defined

The IED slave address referenced in the command is
not defined in the module. Check to make sure there

is an entry in the slave table for each slave device

referenced in the command list.

2

Invalid command

This command is not valid. Check to make sure the
slave address parameter is greater than or equal to

zero and that the point count is not set to zero.

3

Object not supported

The data object in the command is not supported by
the module. Refer to the DNP subset for the Master

Port.

4

Command function not

supported

The function specified in the command is not
supported for the object type selected. Refer to the

DNP subset for the Master Port.

10

Invalid binary input poll

command

This binary input object command is not valid.

11

Invalid binary input event

poll command

This binary input event object poll command is not

valid.

20

Invalid binary output

command function

This binary output command function is not valid.

30

Invalid counter poll

command function

The counter object poll command contains an invalid

function code.

31

Invalid counter poll

command

This counter object poll command is not valid.

40

Invalid frozen counter poll

command

This frozen counter object poll command is not valid.

50

Invalid analog input poll

command

This analog input poll command is not valid.

51

Invalid analog input event

poll command

This analog input event poll command is not valid.

60

Invalid analog output poll

command function

This analog output poll command contains an invalid

function code.

61

Invalid analog output poll

command

This analog output poll command is not valid.

70

Invalid time/date poll

command

This time/date object poll command is not valid.

80

Invalid event poll command This event poll command is not valid.