ProSoft Technology MVI94-DNP User Manual

Page 95

Advertising
background image

MVI94-DNP ♦ Flex I/O

Reference

DNP 3.0 Server over Ethernet Communication Module

User Manual

ProSoft Technology, Inc.

Page 95 of 131

December 17, 2010

5.5

MVI94-DNP Configuration Forms

This section contains configuration forms that will aid in the configuration of the

module. If you design your system before trying to directly implement it, you will

have a greater chance of success. Fill in the configuration forms for your

application, and then edit the configuration text file. This section contains forms

for both master and slave configuration:

5.5.1 Slave Configuration

Variable
Name

Data
Range

Description

IF Error

Config.
Value

[Module]

This section header indicates the start of the module specific

parameter set.

Module Name: 80

Characters

This parameter sets the name or description
of the module’s application

"Not
Configured

"

Type:

M=Master

or S=Slave

This parameter must be set to M for the

DNP port to be used as a master port. If the
parameter is set to any other value, the port

will be used as a slave port.

S

Slave

Variable
Name

Data
Range

Description

IF Error

Config.
Value

[DNP Slave]

This section header defines the start of the DNP slave parameter set.

Internal Slave

ID:

0 to 65534 This is the DNP address for the module. All

messages with this address from the master

will be processed by the module.

65534

Baud Rate:

Baud Rate
from Table

Port Baud Rate: 300, 600, 1200, 2400,
4800, 9600, 19200, 384 (38400), 576

(57600), 115 (115200)

9600

RTS On:

0 to 65535 This value represents the number of 1 ms

increments to be inserted between

asserting the RTS modem line and the
actual transmission of the data.

NA

RTS Off:

0 to 65535 This value represents the number of 1 ms

increments to be inserted after the last

character of data is transmitted before the
RTS modem line is dropped.

NA

Min Response
Delay:

0 to 65535 Minimum time between receiving a request

and transmitting a response. Allows master

time to disable transmitter on an RS-485

network.

NA

Modem:

Y or N

This parameter defines if a dial-up modem
is used on the DNP slave port. If the value

is set to N, no modem is used. If the

parameter is set to Y, a modem is used.

N

Connect

Timeout:

0 to 65535 Defines the number of milliseconds to wait

for the CD signal to be set high. The CD
signal indicates a connection is made using

a dial-up modem.

NA