ProSoft Technology MVI94-DNP User Manual

Page 102

Advertising
background image

Reference

MVI94-DNP ♦ Flex I/O

User Manual

DNP 3.0 Server over Ethernet Communication Module

Page 102 of 131

ProSoft Technology, Inc.

December 17, 2010

Variable
Name

Data Range

Description

IF Error

Config.
Value

Initialize IED

Database:

Y or N

This parameter defines if the BI/AI/C data
will be transferred from the processor to

the module before normal data transfer

occurs. Set the parameter to N to not use
the feature. Set the parameter Y to use

the feature. The use of this feature

requires ladder logic to transfer the data.

N

Variable
Name

Data Range

Description

IF Error

Config.
Value

[IED

Database]

This section header defines the start of the DNP master parameter

set.

Binary Inputs: 0 to 960

Number of binary input points contained in
the IED database to transfer to the PLC

and obtained from the attached IED units..

0

Binary

Outputs:

0 to 960

Number of binary output points contained
in the IED database which are transferred

from the PLC and used by the attached

IED units..

0

Counters:

0 to 30

Number of counter points contained in the
IED database to transfer to the PLC and

obtained from the attached IED units..

0

Analog

Inputs:

0 to 120

Number of analog input points contained

in the IED database to transfer to the PLC

and obtained from the attached IED units..

0

Analog

Outputs:

0 to 60

Number of analog output points contained
in the IED database which are transferred

from the PLC and used by the attached

IED units..

0

Variable
Name

Data Range

Description

[DNP Master

Slave List]

This section header defines the location of the DNP master slave

definition list.

# DL Conf Mode ==> 0=Never, 1=Sometimes and 2=Always (select 0).

# Flag parameter is bit coded as follows:

# Bit 0 (decimal 1) ==> Enable the slave

# Bit 1 (decimal 2) ==> Use Unsolicited messaging with this slave

# Bit 2 (decimal 4) ==> Use delay measurement with this slave

# Bit 3 (decimal 8) ==> Auto time synchronization enabled

START

This string signals the start of the slave definition list.

# Node DL Conf Conf Conf App Rsp

# Address Mode Timeout Retry Timeout Flags

2 0 1000 0 5000 9

END

This string signals the end of the slave definition list.