ProSoft Technology MVI94-DNP User Manual

Page 106

Advertising
background image

Reference

MVI94-DNP ♦ Flex I/O

User Manual

DNP 3.0 Server over Ethernet Communication Module

Page 106 of 131

ProSoft Technology, Inc.

December 17, 2010

OBJECT

REQUEST

RESPONSE

Obj

Var Description

Func
Codes

Qual
Codes
(hex)

Func
Code
s

Qual
Codes
(hex)

Data
Size
(bits
)

NOTES

7

32-Bit Delta Counter Without
Flag

129,
130

00, 01

32

Master will process this
variation

8

16-Bit Delta Counter Without
Flag

129,
130

00, 01

16

Master will process this
variation

21

0

Frozen Counter - All
Variations

1

06

32

Master will generate this
variation

1

32-Bit Frozen Counter

129,
130

00, 01

40

Master will process this
variation

2

16-Bit Frozen Counter

129,
130

00, 01

24

Master will process this
variation

3

32-Bit Frozen Delta Counter

40

4

16-Bit Frozen Delta Counter

24

5

32-Bit Frozen Counter With
Time Of Freeze

88

6

16-Bit Frozen Counter With
Time Of Freeze

72

7

32-Bit Frozen Delta Counter
With Time Of Freeze

88

8

16-Bit Frozen Delta Counter
With Time Of Freeze

72

9

32-Bit Frozen Counter
Without Flag

1

06

129,
130

00, 01

32

Master will generate and
process this variation

10

16-Bit Frozen Counter
Without Flag

1

06

129,
130

00, 01

16

Master will generate and
process this variation

11

32-Bit Frozen Delta Counter
Without Flag

32

12

16-Bit Frozen Delta Counter
Without Flag

16

22

0

Counter Change Event - All
Variations

1

06, 07,
08

Master will not generate a
request for this variation

1

32-Bit Counter Change Event
Without Time

129,
130

17, 28

40

Master will process this
variation

2

16-Bit Counter Change Event
Without Time

129,
130

17, 28

24

Master will process this
variation

3

32-Bit Delta Counter Change
Event Without Time

40

4

16-Bit Delta Counter Change
Event Without Time

24

5

32-Bit Counter Change Event
With Time

88

6

16-Bit Counter Change Event
With Time

72

7

32-Bit Delta Counter Change
Event With Time

88

Advertising