MVI94-DNP ♦ Flex I/O

Diagnostics and Troubleshooting

DNP 3.0 Server over Ethernet Communication Module

User Manual

ProSoft Technology, Inc.

Page 63 of 131

December 17, 2010

System Configuration Errors

Error Code Name

Description

100

Too many binary input

points

Too many binary input points are configured for the

module. Maximum value is 15360.

101

Too many binary output

points

Too many binary output points are configured for the

module. Maximum value is 15360.

102

Too many counter points

Too many counter points are configured for the

module. Maximum value is 480.

103

Too many analog input

points

Too many analog input points are configured for the

module. Maximum value is 960.

104

Too many analog input

points

Too many analog output points are configured for the

module. Maximum value is 960.

105

Too many binary input

events

Too many binary input events are configured for the

module. Maximum value is 400.

106

Too many analog input

events

Too many analog input events are configured for the

module. Maximum value is 400.

107

Invalid analog input

deadband

Deadband value for analog input events is out of

range. Value must be in the range of 0 to 32767.

108

Not enough memory

There is not enough memory in the module to

configure the module as specified.

109

Invalid block transfer delay
for blocks 251 and 252

(error/status blocks)

Block transfer delay value specified is too low.

110

File count invalid

The file count must be in the range of 0 to 6.

111

Invalid file record size

The file record size must be in the range of 1 to 120.

112

Invalid block identification

code for file

The file block transfer code must be in the range of

100 to 120.