5.1.3 Functional Specifications

The module has two DNP protocol ports that can be user configured to operate in

a Master/Slave or in a Slave/Slave redundant port configuration.
User defined internal register space is accessible to the protocol driver and to the

FLEX processor memory.

DNP 3.0 Slave Protocol Specifications
The DNP Slave port(s) accepts DNP commands to control and monitor data

stored in the module’s DNP Slave databases. If a DNP Master port is also

configured, a portion of these slave databases can be derived from or can control

IED devices connected to the DNP master port.
 Report-by-Exception data is logged to the module’s database
 Supports unsolicited messaging
 Each DNP point type is user configurable by point
 Class assignments are completely user-definable on a Type and point basis

(BI, AI, FI, DI point types)

 Supports clock synchronization from a master or from the processor
 Up to 400 events are stored for Floats, Binary In, Analog In and Double

Inputs

 Collision avoidance algorithm per DNP organization for redundant port

switching (redundant slave mode)

 Special modem AT command string and timing support for dialing out on

redundant port (redundant slave mode)

DNP 3.0 Master Protocol Specifications
The DNP 3.0 Master port can be configured as a virtual DNP Master device that

actively issues user-defined DNP commands to nodes on the network.
 The Master port supports 300 user defined commands, each one containing

its own set of data link and application layer characteristics

 Master port logically supports up to 40 slave devices
 Individual command configuration includes conditional or continuous polling

and Poll Delay Time

 Slave status and Command status available for transfer to the processor
 Event data received from the slave devices updates the module database

(Date and Time stamping is not stored or used by module)

 Special command handling for Digital Output CROB under processor control

for pulse output control