OBJECT

REQUES
T

RESPONSE

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits
)

NOTES

4

16-Bit Delta Counter Change
Event Without Time

24

Slave will return Unknown
Object to this request

5

32-Bit Counter Change
Event With Time

88

Slave will return Unknown
Object to this request

6

16-Bit Counter Change
Event With Time

72

Slave will return Unknown
Object to this request

7

32-Bit Delta Counter Change
Event With Time

88

Slave will return Unknown
Object to this request

8

16-Bit Delta Counter Change
Event With Time

72

Slave will return Unknown
Object to this request

23

0

Frozen Counter Event - All
Variations

Slave will return Unknown
Object to this request

1

32-Bit Frozen Counter Event
Without Time

40

Slave will return Unknown
Object to this request

2

16-Bit Frozen Counter Event
Without Time

24

Slave will return Unknown
Object to this request

3

32-Bit Frozen Delta Counter
Event Without Time

40

Slave will return Unknown
Object to this request

4

16-Bit Frozen Delta Counter
Event Without Time

24

Slave will return Unknown
Object to this request

5

32-Bit Frozen Counter Event
With Time

88

Slave will return Unknown
Object to this request

6

16-Bit Frozen Counter Event
With Time

72

Slave will return Unknown
Object to this request

7

32-Bit Frozen Delta Counter
Event With Time

88

Slave will return Unknown
Object to this request

8

16-Bit Frozen Delta Counter
Event With Time

72

Slave will return Unknown
Object to this request

30

0

Analog Input - All Variations

1

06

16

Slave will respond with
variation 4 data

1

32-Bit Analog Input

1

06

129,
130

00, 01

40

Slave will return this
variation (Note: Data will
only be 16-bit)

2

16-Bit Analog Input

1

06

129,
130

00, 01

24

Slave will return this
variation

3

32-Bit Analog Input Without
Flag

1

06

129,
130

00, 01

32

Slave will return this
variation (Note: Data will
only be 16-bit)

4

16-Bit Analog Input Without
Flag

1

06

129,
130

00, 01

16

Slave will return this
variation

5

Short Floating Point Analog
Input

1

06

129,
130

00, 01

40

Slave will return this
variation

6

Long Floating Point Analog
Input

1

06

129,
130

00, 01

72

Slave will return this
variation