ProSoft Technology MVI94-DNP User Manual

Page 59

Advertising
background image

MVI94-DNP ♦ Flex I/O

Diagnostics and Troubleshooting

DNP 3.0 Server over Ethernet Communication Module

User Manual

ProSoft Technology, Inc.

Page 59 of 131

December 17, 2010

Word

Block
Number

Block
Offset

Variable Name

Description

21

203

5

Total blocks transferred

Total BTR/BTW or side-connect
interface transfers attempted by the

module.

22

203

6

Successful blocks

transferred

This value represents the total number
of transfer operations between the PLC

and module that are successful.

23

203

7

Total errors in block

transfer

Total number of transfers that resulted

in an error condition.

24

204

2

Total BTR or write errors Total number of BTR or write transfers

that resulted in an error.

25

204

3

Total BTW or read errors Total number of BTW or read transfers

that resulted in an error.

26

204

4

Block number error

Number of BTW requests that resulted

in an incorrect BTW identification code.

27

204

5

Continuous block error

counter

Count of sequential data transfer
errors. When this value exceeds that

specified for the data transfer
operation, the error flag below will be

set.

28

204

6

Block transfer error flag

This flag indicates that data is not being
successfully transferred between the

PLC and the module. This flag

corresponds to the Device Trouble IIN

bit.

29

204

7

Configuration Type

This is a coded field that defines the
configuration of the module. The codes

are as follows: 1=Slave Configuration,

2=Master Configuration

30 to 31 205

2 to 3

Product Name (ASCII)

These two words contain the product

name of the module in ASCII format.

32 to 33 205

4 to 5

Revision (ASCII)

These two words contain the product
revision level of the firmware in ASCII

format.

34 to 35 205

6 to 7

Operating System

Revision (ASCII)

These two words contain the module’s
internal operating system revision level

in ASCII format.

36 to 37 206

2 to 3

Production Run Number

(ASCII)

These two words contain the
production "batch" number for the

particular chip in the module in ASCII

format.

38

206

4

DNP Master Port Slave

Count

This is the total number of slaves
configured for the DNP Master port.

This may not represent the number of

active slaves as it includes slaves that

are not enabled.

39

206

5

DNP Master Port

Command Count

This is the total number of commands
configured for the DNP Master port.

This may not represent the number of

active commands as it includes

commands that are disabled.

Advertising