ProSoft Technology MVI94-DNP User Manual

Page 98

Advertising
background image

Reference

MVI94-DNP ♦ Flex I/O

User Manual

DNP 3.0 Server over Ethernet Communication Module

Page 98 of 131

ProSoft Technology, Inc.

December 17, 2010

Variable
Name

Data
Range

Description

IF Error

Config.
Value

Unsolicited
Response:

Y or N

Set if the slave unit will send unsolicited
response messages. If set to N, the slave

will not send unsolicited responses. If set to

Y, the slave will send unsolicited responses.
This feature requires collision avoidance on

a multi-drop network.

N

Class 1 Unsol
Resp Min:

1 to 255
events

Minimum number of events in Class 1
required before an unsolicited response will

be generated (not implemented).

10

Class 2 Unsol
Resp Min:

1 to 255
events

Minimum number of events in Class 2
required before an unsolicited response will

be generated (binary input events).

25

Class 3 Unsol

Resp Min:

1 to 255

events

Minimum number of events in Class 3

required before an unsolicited response will

be generated (analog input events).

25

Unsol Resp
Delay:

0 to 65535
millisecond

s

Maximum number of 1 millisecond intervals
to wait after an event occurs before sending

an unsolicited response message. If set to

0, only use minimum number of events.

NA

Uresp Master
Address:

0 to 65534 DNP destination address where unsolicited

response messages are sent.

65534

AI Events with
time:

Y or N

This parameter determines if the analog
input events are to be returned with a time

value. If the parameter is set to N, no time

will be returned with the event. If the
parameter is set to Y, a time will be

returned.

N

Time Sync

Before

Events:

Y or N

This parameter defines if the remote DNP

master must synchronize the time before

events are generated by the slave. If the
parameter is set to N, this synchronization

is not required. If set to Y, the

synchronization is required.

N

Initialize DNP

BO/AO:

Y or N

This parameter defines if the binary and

analog outputs are to be read from the
processor before the program starts its

normal data transfer. If the parameter is set

to N, this feature is not implemented. If the

parameter is set to Y, the feature is used
and special ladder logic must be

implemented to transfer the data from the

processor to the module.

N

Variable
Name

Data
Range

Description

IF Error

Config.
Value

[DNP Slave

Database]

This section header defines the start of the DNP slave database

definition parameter set.

Binary Inputs: 0 TO 960

Number of digital input points to configure in
the DNP slave device. Each point will be

stored as a single bit in the module

memory.

0

Advertising