3 Press [Y]. The module will automatically start a Zmodem file transfer. The
configuration file will be stored in the default file transfer folder on your PC.
Note: ProSoft Technology suggests that you download the configuration file pre-loaded on
your module. However, configuration files are also available on the ProSoft CD as well as the
ProSoft Technology web site at www.prosoft-technology.com.
When the configuration file has been transferred to your PC, the dialog box
will indicate that the transfer is complete.
The configuration file is now in a folder on your PC. To view the location of
this folder, open the Transfer menu in HyperTerminal and choose Receive
File.
4 You can now open and edit the file in a text editor such as Notepad. When
you have finished editing the file, save it and close Notepad.
Important: You must name this file DNP.CFG before you transfer it to the module. The module will
not recognize configuration files with any other name or extension.