Reference

MVI94-DNP ♦ Flex I/O

User Manual

DNP 3.0 Server over Ethernet Communication Module

Page 90 of 131

ProSoft Technology, Inc.

December 17, 2010

Set Processor Time Block (9970)
This block is constructed by the processor to request the module’s time. The

following table describes the format of this block.

Word Offset in Block Data Field(s)

Description

0

Block ID

This field contains the value of 9970 identifying
the block type to the module.

1 to 6

Not Used

Not Used

When the module receives this block, it immediately constructs a response block

containing the modules current time. The following table describes the format of

this block.

Word Offset in Block Data Field(s)

Description

0

Block Read ID

This field contains the block identification code of

9970 for the block.

1

Block Write ID

This is the next block requested by the module.

2

Year

This field contains the four-digit year for the new
time value.

3

Month

This field contains the month value for the new

time. Valid entry for this field is in the range of 1

to 12.

4

Day

This field contains the day value for the new time.
Valid entry for this field is in the range of 1 to 31.

5

Hour

This field contains the hour value for the new
time. Valid entry for this field is in the range of 0

to 23.

6

Minute

This field contains the minute value for the new
time. Valid entry for this field is in the range of 0

to 59.

7

Seconds

This field contains the second value for the new

time. Valid entry for this field is in the range of 0

to 59.