MVI94-DNP ♦ Flex I/O

User Manual

DNP 3.0 Server over Ethernet Communication Module

Page 84 of 131

ProSoft Technology, Inc.

December 17, 2010

CROB Control Block for Digital Outputs (Block 9901)
The CROB (Control Relay Output Block) controls a digital output on an IED unit

connected to a master port under program control. This block provides more

control than the binary output control offered in the command list. The selected

point can use the pulse on/off feature of the DNP protocol using this block. Refer

to the Basic 4 documentation for a full discussion of the CROB object and its

functionality. The structure of the block sent from the processor to the module is

shown in the following table.

Word Offset in Block Data Field(s)

Description

0

Block ID

This field contains the block identification code of
9901 for the block.

1

Slave Address

This is the IED node address for the slave to
consider on the network.

2

Function

Function codes 3, 5 and 6 supported. Function

code 4 is automatically sent after a successful
function 3.

3

Address in Slave

Point in IED to consider with the CROB.

4

Control Code

This is a standard DNP protocol control code
byte (see description below).

5

Pulse Count

This parameter specifies the number of pulses to

generate for pulse output control. This parameter

has a range of 0 to 255 as the value is a byte
parameter in the CROB. If a value of zero is

entered, the operation will not execute.

6

Pulse On/Off Time

This parameter specifies the on-time and off-time

intervals for pulse control. The same time value is
used for both parameters in the constructed

CROB message.

The Control Code field of the block defines the method of output control. This bit-

mapped value has the following definition:

Bits

Definitions

Description

0 to 3

Code

These bits determine the control operation to be
performed by the command: 0=No operation,

1=Pulse on, 2=Pulse off, 3=Latch on and 4=Latch
off. All other values are undefined in the DNP

protocol.

4

Queue

0=Normal (execute once), 1=Requeue (place at

end of queue after operation).

5

Clear

This parameter clears the queue. If the value is
set to zero, the queue is not affected. If the value

is set to 1, the queue will be cleared.

6 to 7

Trip/Close

These two bits select the trip or close relay. For
close relay control, set the bits to 01. For trip

relay control, set the bits to 10. A value of 00 for
the bits is used for single point control of normal

digital output points.

When the module receives this block, it will place the request in the command

queue as long as there is room in the queue for the command. This will cause

the command to be executed at a high priority. The module does not send a

response message back to the processor for this block.