ProSoft Technology MVI94-DNP User Manual
Page 119

MVI94-DNP ♦ Flex I/O
Reference
DNP 3.0 Server over Ethernet Communication Module
User Manual
ProSoft Technology, Inc.
Page 119 of 131
December 17, 2010
Time-outs while waiting for:
Data Link Confirm
: Configurable at module start-up (1 to 65535 mSec)
Complete Application Fragment
: Configurable at module start-up
Application Confirm
: Configurable at module start-up (1 to 65535 mSec)
Complete Application Response : None
Sends/Executes Control Operations:
WRITE Binary Outputs
: Never
SELECT/OPERATE
: Always
DIRECT OPERATE
: Always
DIRECT OPERATE-NO ACK
: Always
Count > 1
: Always (1 to 65535)
Pulse On
: Always
Pulse Off
: Always
Latch On
: Always
Latch Off
: Always
Queue
: Never
Clear Queue
: Never
Reports Binary Input Change Events when no
Reports time-tagged Binary Input Change Events
specific variation requested:
when no specific variation requested:
Only time-tagged
Binary Input Change with Time
Sends Unsolicited Responses:
Sends Static Data in Unsolicited Responses:
This is configurable at module start-up. If the
Never
number of events for the Binary or Analog Input
Events is greater than 0, unsolicited responses
are supported. Use the Enable/Disable
Unsolicited function code from the DNP master for
control.
Default Counter Object/Variation:
Counters Roll Over at:
Object
: 20
32 Bits
Variation : 5
Sends Multi-Fragment Responses: Yes