1) how to make a restart after a stop by the, Key input from the pu – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 104

Advertising
background image

95

2

(1) How to make a restart after a stop by the

STOP

RESET

key input from the

operation panel (Restarting method with

shown)

1) After completion of deceleration to

a stop, switch off the STF or STR
signal.

2) Press the

PU

EXT

key to

show

PU

. ........ (

canceled)

3) Press the

PU

EXT

key to return to

EXT

.

4) Switch on the STF or STR signal.

S

peed

Time

key

Stop and restart example for external operation

Control panel

key

PU

EXT

STOP

RESET

STF ON

(STR) OFF

REMARKS

By entering the reset signal (RES) during operation, the inverter shuts off its

output while it is reset, the internal thermal summation value of the electronic
overcurrent protection and the number of retries are reset, and the motor coasts.

The Pr. 75 value can be set any time. Also, if parameter (all) clear is executed,

this setting will not return to the initial value.

When the inverter is stopped by the PU stop function, the display alternates

between

and

. An alarm is not output.

(2) How to make a restart when a stop is made by the

STOP

RESET

key

input from the PU

1) After completion of deceleration

to a stop, switch off the STF or
STR signal.

2) Press the

EXT

key

. ..................... (

canceled)

3) Switch on the STF or STR signal.

Time

key

key

STOP

RESET

EXT

S

peed

Control panel

STF ON

(STR) OFF

Stop and restart example for external operation

Besides the above operations, a restart can be made by performing a power-on reset
or resetting the inverter with the inverter's reset terminal.

REMARKS

By entering the reset signal (RES) during operation, the inverter shuts off output

while it is reset, the data of the electronic overcurrent protection and regenerative
brake duty are reset, and the motor coasts.

To resume operation, reset the inverter after confirming that the PU is connected

securely.

The Pr. 75 value can be set any time. Also, if parameter (all) clear is executed,

this setting will not return to the initial value.

When the inverter is stopped by the PU stop function, PS is displayed but an

alarm is not output.

Advertising
This manual is related to the following products: