<Setting>

In the following table, operation using the control panel or parameter unit is
abbreviated to PU operation.

LED Indication *

RUN

PU

EXT

Pr. 79

Setting

Function

RUN

PU

EXT

0

At power-on, the inverter is put in the external
operation mode. The operation mode can be
changed between the PU and external operation

modes from the operation panel (

PU

EXT

key) or

parameter unit (

PU

/

EXT

key). For each mode,

refer to the columns of settings 1 and 2.

Refer to
settings "1"
and "2".

Operation

mode

Running frequency

Start

signal

1

PU operation
mode

Setting from operation
panel or FR-PU04

RUN

key

On

(Off)

Off

Off: Stop without start

command

Forward rotation: On
Reverse rotation:
Slow flickering

2

External
operation
mode

External signal input
(across terminals
2(4)-5, multi-speed
selection, jog)

External
signal input
(terminal
STF, STR)

Off

On

With start
command
Without
frequency
setting

Fast

flickering

3

External/ PU
combined
operation
mode 1

Dial of operation
panel, digital setting by
parameter unit key
operation, or external
signal input (multi-
speed setting, across
terminals 4-5 (valid
when AU signal is on))

External
signal input
(terminal
STF, STR)

4

External/ PU
combined
operation
mode 2

External signal input
(across terminals
2(4)-5, multi-speed
selection, jog)

RUN

key

On

On

7

External operation mode (PU operation interlock)
MRS signal ON ... Able to be switched to PU

operation mode (output stop
during external operation)

MRS signal OFF .. Switching to PU operation

mode inhibited

8

Operation mode change using external signal
(disallowed during operation)
X16 signal ON ..... Switched to external

operation mode

X16 signal OFF.... Switched to PU operation mode

Refer to
settings "1"
and "2".

REMARKS

Either "3" or "4" may be set to select the PU/external combined operation. These
settings differ in starting method.
In case of the type having the RS-485 communication function, refer to page 116 for
the computer link operation mode.

*1. When the FR-PU04 is connected, the LED indication (PU, EXT) is not lit.
*2. The LED indication (PU, EXT) flickers in the computer link operation mode.
*3. Lit when the operation panel is used. Extinguished when the FR-PU04 is used.