MITSUBISHI ELECTRIC FR-S520 User Manual

Page 149

Advertising
background image

140

3

Operation Panel Indication

GF

FR-PU04

Ground Fault

Name

Start-time output side ground fault overcurrent protection

Description

This function stops the inverter output if a ground fault overcurrent
flows due to a ground fault which occurred in the inverter's output
(load) side. Made valid when Pr. 40 "start-time ground fault
detection selection" = "1".

Check point

Check for a ground fault in the motor and connection cable.

Corrective action

Remedy the ground fault portion.

Operation Panel Indication

OHT

FR-PU04

OH Fault

Name

External thermal relay (*2)

Description

If the external thermal relay designed for motor overheat
protection or the internally mounted temperature relay in the
motor switches on (contacts open), the inverter output is stopped.
If the relay contacts are reset automatically, the inverter will not
restart unless it is reset.

Check point

Check for motor overheating.
Check that the value of 7 (OH signal) is set correctly in any of
Pr. 60 to Pr. 63 (input terminal function selection).

Corrective action

Reduce the load and operating duty.

*2. Functions only when any of Pr. 60 to Pr. 63 (input terminal function selection) is

set to OH.

Operation Panel Indication

OLT

FR-PU04

Stll Prev STP

Name

Stall prevention (overload)

Description

The running frequency has fallen to 0 by stall prevention
operation activated. OL appears while stall prevention is being
activated.

Check point

Check the motor for use under overload.

Corrective action

Reduce the load weight.

Operation Panel Indication

OPT

FR-PU04

Option Fault

Name

Communication error (*3)

Description

Stops the inverter output if a setting error or connection
(connector) fault occurs during use of the RS-485 communication
function.

Check point

Check that the connector is plugged securely.

Corrective action

Make connection securely.
Please contact your sales representative.

Operation Panel Indication

PE

FR-PU04

Corrupt Memory

Name

Parameter error

Description

A fault occurred in parameters stored
(example: E

2

PROM fault).

Check point

Check for too many number of parameter write times.

Corrective action

Please contact your sales representative.