Checking the inverter and converter modules
<Preparation>
(1) Disconnect the external power supply cables (R, S, T) and motor cables (U, V, W).
(2) Prepare a meter. (Use 100
Ω
range.)
<Checking method>
Change the polarity of the meter alternately at the inverter terminals R, S,
T, U, V, W, P and N, and check for continuity.
CAUTION
Before measurement, check that the smoothing capacitor is discharged.
At the time of continuity, the measured value is several to several ten's-of ohms
depending on the number of modules, number of parallel modules, circuit tester
type, etc. If all measured values are almost the same, the modules are without
fault.
<Module device numbers and terminals to be checked>
Tester Polarity
Tester Polarity
Measured
Value
Measured
Value
R
P
Discontinuity
R
N
Continuity
D1
P
R
Continuity
D4
N
R
Discontinuity
S
P
Discontinuity
S
N
Continuity
D2
P
S
Continuity
D5
N
S
Discontinuity
T
P
Discontinuity
T
N
Continuity
Conv
er
te
r
modul
e
D3
P
T
Continuity
D6
N
T
Discontinuity
U
P
Discontinuity
U
N
Continuity
TR1
P
U
Continuity
TR4
N
U
Discontinuity
V
P
Discontinuity
V
N
Continuity
TR3
P
V
Continuity
TR6
N
V
Discontinuity
W
P
Discontinuity
W
N
Continuity
In
v
e
rte
r
modul
e
TR5
P
W
Continuity
TR2
N
W
Discontinuity
(Assumes the use of an analog meter.)
Converter
module
Inverter module
D1
D2
D3
D4
D5
D6
TR1
TR3
TR5
TR4
TR6
TR2
U
V
W
R
S
T
C
P
N
REMARKS
The FR-S520S-0.1K to 1.5K and FR-S510W-0.1K to 0.75K do not have T, D3 and D6.