Checking method, Module device numbers and terminals to be checked – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 162

Advertising
background image

153

Checking the inverter and converter modules

<Preparation>

(1) Disconnect the external power supply cables (R, S, T) and motor cables (U, V, W).
(2) Prepare a meter. (Use 100

range.)

<Checking method>

Change the polarity of the meter alternately at the inverter terminals R, S,
T, U, V, W, P and N, and check for continuity.

CAUTION

Before measurement, check that the smoothing capacitor is discharged.
At the time of continuity, the measured value is several to several ten's-of ohms
depending on the number of modules, number of parallel modules, circuit tester
type, etc. If all measured values are almost the same, the modules are without
fault.

<Module device numbers and terminals to be checked>

Tester Polarity

Tester Polarity

Measured

Value

Measured

Value

R

P

Discontinuity

R

N

Continuity

D1

P

R

Continuity

D4

N

R

Discontinuity

S

P

Discontinuity

S

N

Continuity

D2

P

S

Continuity

D5

N

S

Discontinuity

T

P

Discontinuity

T

N

Continuity

Conv

er

te

r

modul

e

D3

P

T

Continuity

D6

N

T

Discontinuity

U

P

Discontinuity

U

N

Continuity

TR1

P

U

Continuity

TR4

N

U

Discontinuity

V

P

Discontinuity

V

N

Continuity

TR3

P

V

Continuity

TR6

N

V

Discontinuity

W

P

Discontinuity

W

N

Continuity

In

v

e

rte

r

modul

e

TR5

P

W

Continuity

TR2

N

W

Discontinuity

(Assumes the use of an analog meter.)

Converter

module

Inverter module

D1

D2

D3

D4

D5

D6

TR1

TR3

TR5

TR4

TR6

TR2

U

V

W

R

S

T

C

P

N

REMARKS

The FR-S520S-0.1K to 1.5K and FR-S510W-0.1K to 0.75K do not have T, D3 and D6.