Reverse rotation prevention selection

This function can prevent any reverse rotation fault resulting from the incorrect

input of the start signal.

POINT

Used for a machine which runs only in one direction, e.g. fan, pump.

(The setting of this function is valid for the combined, PU, external and

communication operations.)

Parameter

Name

Factory

Setting

Setting

Range

Remarks

78

Reverse rotation

prevention

selection

0

0, 1, 2

Setting is enabled when Pr. 30 = "1"

<Setting>

Pr. 78 Setting

Function

0

Both forward and reverse rotations allowed

1

Reverse rotation disallowed

2

Forward rotation disallowed

2

.10.10

Operation mode selection

Used to select the operation mode of the inverter.

The inverter can be run from the control panel or parameter unit (PU operation),

with external signals (external operation), or by combination of PU operation and

external operation (external/PU combined operation).

The inverter is placed in the external operation mode at power-on (factory setting).

Parameter

Name

Factory Setting

Setting Range

79

Operation mode selection

0

0 to 4, 7, 8