Operation Panel Indication

OC2

FR-PU04

Stedy Spd OC

Name

Overcurrent cut-off during constant speed

Description

When the inverter output current reaches or exceeds
approximately 200% of the rated inverter current during constant-
speed operation, the protective circuit is activated to stop the
inverter output.

Check point

Check for sudden load change.
Check for output short-circuit/ground fault.

Corrective action

Keep load stable.

Operation Panel Indication

OC3

FR-PU04

OC During Dec

Name

Overcurrent cut-off during deceleration

Description

When the inverter output current reaches or exceeds
approximately 200% of the rated inverter current during
deceleration (other than acceleration or constant speed), the
protective circuit is activated to stop the inverter output.

Check point

Check for sudden speed reduction.
Check for output short-circuit/ground fault.
Check for too fast operation of motor's mechanical brake.

Corrective action

Increase the deceleration time.
Adjust brake operation.

Operation Panel Indication

OV1

FR-PU04

OV During Acc

Name

Regenerative overvoltage cut-off during acceleration

Description

When the main circuit DC voltage in the inverter rises to or above
the specified value due to excessive regenerative energy during
acceleration, the protective circuit is activated to stop the inverter
output. The circuit may also be activated by a surge voltage
produced in the power supply system.

Check point

Check for too slow acceleration.

Corrective action

Decrease the acceleration time.
Install a power factor improving reactor.

Operation Panel Indication

OV2

FR-PU04

Stedy Spd OV

Name

Regenerative overvoltage cut-off during constant speed

Description

When the main circuit DC voltage in the inverter rises to or above
the specified value due to excessive regenerative energy during
constant speed, the protective circuit is activated to stop the
inverter output. The circuit may also be activated by a surge
voltage produced in the power supply system.

Check point

Check for sudden load change.

Corrective action

Keep load stable.
Install a power factor improving reactor.