4) i/o signals, 5) parameter setting – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 114

Advertising
background image

105

2

(4) I/O signals

Signal

Terminal Used

Function

Description

X14

Depending on

Pr. 60 to Pr. 63

PID control

selection

Turn on X14 to exercise PID control.

2

2

Set point input

Enter the set point for PID control.

Input

4

4

Process value

input

Enter the 4 to 20mADC process value

signal from the detector.

FUP

Upper limit output

Output to indicate that the process value

signal exceeded the upper limit value.

FDN

Lower limit output

Output to indicate that the process value

signal exceeded the lower limit value.

Output

RL

Depending on

Pr. 64, Pr. 65

Forward (reverse)

rotation direction

output

"Hi" is output to indicate that the output

indication of the parameter unit is forward

rotation (FWD) or "Low" to indicate that it is

reverse rotation (REV) or stop (STOP).

Enter the set point across inverter terminals 2-5 or in Pr. 93 and enter the process
value signal across inverter terminals 4-5.
To exercise PID control, turn on the X14 signal. When this signal is off, PID control is
not exercised.

Item

Entry

Description

Set 0V as 0% and 5V as 100%.

When "0" is set in Pr. 73 (5V

selected for terminal 2).

Across

terminals 2-5

Set 0V as 0% and 10V as 100%.

When "1" is set in Pr. 73 (10V

selected for terminal 2).

Set point

Pr. 93

Set the set point (%) in Pr. 93.

Process

value

Across

terminals 4-5

4mA DC is equivalent to 0% and 20mA DC to 100%.

(5) Parameter setting

Parameter

Number

Name

Setting

Description

20

For heating, pressure control, etc. PID reverse action

88

PID action

selection

21

For cooling, etc.

PID forward action

0.1 to 999%

If the proportional band is narrow (parameter setting is

small), the manipulated variable varies greatly with a

slight change of the process value. Hence, as the

proportional band narrows, the response sensitivity

(gain) improves but the stability deteriorates, e.g.

hunting occurs.

Gain K = 1/proportional band

89

PID

proportional

band

- - -

No proportional control

Advertising