MITSUBISHI ELECTRIC FR-S520 User Manual

Page 168

Advertising
background image

159

Item

Measuring Point

Measuring

Instrument

Remarks

(Reference Measured Value)

Frequency setting
power supply

Across 10 (+)-5

5VDC

"5" i

s

c

o

mmon.

Across FM (+)-SD

Approximately 5VDC at
maximum frequency
(without frequency meter)

8VDC

T1

T2

Pulse width T1:

Adjusted with C1

Pulse cycle T2:

Set with Pr. 55 (Pr,56)

SD i

s

c

o

mmon.

Frequency meter
signal

Across AM (+)-5

Moving-coil type
(Meter, etc. may be
used)
(Internal resistance:
50k

or larger)

Approximately 5VDC at
maximum frequency
(without frequency meter)

5 i

s

c

o

mmon.

Start signal
Select signal

Across STF, STR,
RH, RM, RL, MRS,
RES-SD

Moving-coil type
(Meter, etc. may be
used)
(Internal resistance:
50k

or larger)

20 to 30VDC when open.
ON voltage: 1V or less
SD is common.

SD i

s

c

o

mmon.

Continuity check

<Normal>

<Fault>

Across
A-C:

Discontinuity Continuity

Alarm signal

Across A-C
Across B-C

Moving-coil type
(such as a meter)

Across
B-C:

Continuity Discontinuity

CAUTION

1. Use FFT to measure the output voltage accurately. It can not be measured

accurately with a meter or general instrumentation.

2. When the carrier frequency exceeds 5kHz, do not use the instrument because

overcurrent losses occurring in the metallic parts inside the instrument will
increase and may lead to burnout.
In this case, use an approximate effective value type instrument.