123

2

5) Waiting time

Specify the waiting time between the receipt of data at the inverter from the
computer and the transmission of reply data. Set the waiting time in accordance
with the response time of the computer between 0 and 150ms in 10ms increments
(e.g. 1 = 10ms, 2 = 20ms).

Computer

Inverter

Inverter

Computer

Inverter data processing time
= waiting time + data check time

(setting 10ms)

(12ms)

REMARKS

When communication parameter n7 "waiting time setting"

‚ "- - -", create the

communication request data without "waiting time" in the data format. (The number
of characters is decremented by 1.)

6) Response time

Computer

Inverter
Inverter

Computer


(refer to the following calculation expression)

Inverter data processing time = waiting time + data check time

(set value 10ms)

(12ms)

10ms or
more required

10ms or
more required

(refer to the following calculation expression)

STX

ACK

ENQ

Computer

Inverter
Inverter

Computer


(refer to the following calculation expression)

Inverter data processing time = waiting time + data check time

(set value 10ms)

(12ms)

10ms or
more required

Data sending time

(refer to the following calculation expression)

ENQ

Data sending time

Data sending time

Data sending time

[Data sending time calculation expression]

1

Communication speed

(bps)

Number of data characters

(Refer to page 121)

Communication specification

(Total number of bits)

(See below)

=

Data sending time (s)

Communication specification

Name

Number of Bits

Stop bit length

1 bit
2 bits

Data length

7 bits
8 bits

Yes

1 bit

Parity check

No

0 bits

In addition to the bits in the above table, 1 bit is required for the start bit.
Minimum total number of bits ... 9 bits
Maximum total number of bits ... 12 bits