Parameter

Number

Name

Setting

Description

0.1 to 999s

Time required for the integral (I) action to provide the
same manipulated variable as that for the proportional
(P) action. As the integral time decreases, the set point
is reached earlier but hunting occurs more easily.

90

PID integral

time

- - -

No integral control.

0 to 100%

Set the upper limit. If the feedback value exceeds the
setting, the FUP signal is output. (Process value of
4mA is equivalent to 0% and 20mA to 100%.)

91

PID upper

limit

- - -

No function

0 to 100%

Set the lower limit. (If the feedback value falls below
the setting, the FDN signal is output. In this case, the
process value of 4mA is equivalent to 0% and 20mA to
100%.)

92

PID lower

limit

- - -

No function

93

PID action

set point for

PU operation

0 to 100%

Valid only when Pr. 79 = "3" (n9 = 0 for computer link
operation) under the PU command in the PU operation
or PU/external combined mode. (When the computer
has the speed command write in the computer link
operation mode (NET))
For external operation, the voltage across 2-5 is the
set point.
(C3 value is equivalent to 0% and C4 value to 100%.)

0.01 to 10s

Time required for the differential (D) action to provide
the same process value as that for the proportional (P)
action. As the differential time increases, greater
response is made to a deviation change.

94

PID

differential

time

- - -

No differential control.

(6) Adjustment procedure

Turn on X14 signal.

Parameter setting

Terminal setting

Run

Adjust the PID control parameters, Pr. 88 to Pr. 94.

Set the I/O terminals for PID control.
(Use Pr. 64 and Pr. 65 (output terminal function selection) to set the
FUP and FDN signals.)
(Use any of Pr. 60 to Pr. 63 (input terminal function selection) to set
the X14 signal.)