(2) RS-485 communication

Use the RS-485 connector to perform communication operation from a personal
computer etc.
By connecting the RS-485 connector to a computer such as a personal computer,
Factory Automation unit (HMI etc.) or other computer, by the communication
cable, you can operate/monitor the inverter and read/write the parameter values
using user programs. For parameter setting, refer to page 116.

Conforming standard: EIA Standard RS-485
Transmission format: Multidrop link system
Communication speed: Max. 19200bps
Overall extension: 500m (1640.42feet)

<System configuration examples>

1) When a computer having a RS-485 interface is used with several inverters

Station 1

RS-485
interface
/terminal

Computer

RS-485

connector

(*1)

RS-485

connector

(*1)

RS-485

connector

(*1)

10BASE-T cable (*2)

Distribution
terminal

Inverter

Station 2

Inverter

Station n

Inverter

Termination
resistor

(Max. 32 inverters)

Use the connectors and cables which are available on the market.
Introduced products (as of June, 2000)
*1. Connector :RJ45 connector

Example: 5-554720-3, Tyco Electronics Corporation

*2. Cable

:Cable conforming to EIA568 (such as 10BASE-T cable)

Example: SGLPEV 0.5mm

×

4P (Twisted pair cable, 4 pairs),

Mitsubishi Cable Industries, Ltd.
(Do not use pins No. 2 and 8 (P5S)).

2) When a computer having a RS-232C interface is used with inverters

10BASE-T cable (*2)

RS-485

connector

(*1)

RS-232C
connector

RS-232C
cable

Station 1

Inverter

Station 2

Station n

Computer

Inverter

Inverter

RS-485

connector

(*1)

RS-485

connector

(*1)

RS-485
terminal

Max. 15m

Converter*

Distribution
terminal

Termination
resistor

Commercially available converter is required. (*3)