MITSUBISHI ELECTRIC FR-S520 User Manual

Page 126

Advertising
background image

117

2

2) Operation mode-based functions

Operation Mode

Operation

Location

Item

PU operation

External

operation

Computer link

operation

Run command
(start)

Enabled

Enabled

(Combined

operation mode)

Disabled

Running frequency
setting

Enabled

Enabled

(Combined

operation mode)

Disabled

Monitoring

Enabled

Enabled

Enabled

Parameter write

Enabled (*4)

Disabled

Disabled

Parameter read

Enabled

Enabled

Enabled

Inverter reset

Enabled

Enabled

Enabled

Operation panel
or FR-PU04

Stop command

Enabled

Enabled (*3)

Enabled (*3)

Run command

Disabled

Disabled

Enabled (*1)

Running frequency
setting (*)

Disabled

Disabled

Enabled (*1)

Monitoring

Enabled

Enabled

Enabled

Parameter write

Disabled

Disabled

Enabled (*4)

Parameter read

Enabled

Enabled

Enabled

Inverter reset

Disabled

Disabled

Enabled (*2)

On-computer
user program by
RS-485
communication

Stop command

Disabled

Disabled

Enabled

Inverter reset

Enabled

Enabled

Enabled

Run command

Enabled

(Combined

operation mode)

Enabled

Enabled (*1)

Control circuit
external
terminal

Running frequency
setting

Enabled

(Combined

operation mode)

Enabled

Enabled (*1)

*1. As set in the communication parameters n8 "operation command write" and n9

"speed command write". (refer to page 130)

*2. At occurrence of RS-485 communication error, the inverter cannot be reset

from the computer.

*3. As set in Pr. 75 "reset selection/PU stop selection".
*4. As set in Pr. 77 "parameter write disable selection".

CAUTION

* When the user program of the computer is used to make the running frequency

setting by RS-485 communication, setting can be made in the minimum setting
increments of 0.01Hz, but the setting may be written to the inverter in increments
of 0.1Hz. (0 is written in the second decimal place.)

POINT

To make RS-485 communication between the inverter and personal computer, the
operation mode must be set to the "computer link operation mode".
Pr. 79 "operation mode selection"

‚ "1, 3, 4"

and communication parameter n10 "link start mode selection" = "1"
Reset the inverter after setting the communication parameters n1, n2, n3, n4, n7,