Operation display – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 121

Advertising
background image

112

Changing example

Deflecting the meter (analog indicator) to full-scale (1mA) at the

preset frequency of 60Hz (for frequency setting, refer to the
instruction manual (basic).)

POINT

The calibration parameters "C1" can be made to be ready by setting "1" (extended

function parameter valid) in Pr. 30 "extended function display selection".

Set the value of the calibration parameter C1 "FM terminal calibration".

(For details, refer to the instruction
manual (basic).)

MODE

4.

5.

Press the key to enable setting.

SET

SET

3.

SET

8.

SET

Flicker ... Parameter setting complete!!

SET

6.

RUN

PU

EXT

RUN

RUN

+

-

7.

1.

MODE

Pr. 30 must be set to "1".

2.

Turn the setting dial to show

" "

.

Operation

Display

In PU operation mode

Press the key to show

SET

" "

.

The parameter
number read
previously
appears.

By turning the setting dial , you can read another parameter.

SET

Press the key to return to the indication (step 3).

SET

Press the key twice to show the next parameter ( ).

Press the key to choose the
parameter setting mode.

Turn the setting dial until the
calibration parameter C1 "FM
terminal calibration" appears.

If the inverter is at a stop, press the

Press the key.
Setting is complete.

Turn the

setting dial to

adjust the indicator needle
to the desired position.

Analog indicator

key to start it. (The motor

need not be connected.)

Advertising
This manual is related to the following products: