2) "Harmonic suppression guideline for specific consumers"

This guideline sets forth the maximum values of harmonic currents outgoing from a
high-voltage or specially high-voltage consumer who will install, add or renew
harmonic generating equipment. If any of the maximum values is exceeded, this
guideline requires that consumer to take certain suppression measures.

Table 1 Maximum Values of Outgoing Harmonic Currents per 1kW Contract Power

Received Power Voltage

5th

7th

11th

13th

17th

19th

23rd

Over

23rd

6.6kV

3.5

2.5

1.6

1.3

1.0

0.9

0.76

0.70

22 kV

1.8

1.3

0.82

0.69

0.53

0.47

0.39

0.36

33 kV

1.2

0.86

0.55

0.46

0.35

0.32

0.26

0.24

(1) Application of the harmonic suppression guideline for specific

consumers

Not more than
reference capacity

New installation/addition/
renewal of equipment

Calculation of equivalent
capacity sum

Sum of equivalent
capacities

Over reference
capacity

Calculation of outgoing
harmonic current

Is outgoing harmonic
current equal to or lower
than maximum value?

Not more than
maximum value

Harmonic suppression
technique is not required.

Over maximum value

Harmonic suppression
technique is required.