(3) Selecting the rated sensitivity current for the earth leakage circuit

breaker

When using the earth leakage circuit breaker with the inverter circuit, select its rated
sensitivity current as follows, independently of the PWM carrier frequency:

Progressive Super Series
(Type SP, CF, SF, CP)
Rated sensitivity current:
I

n

10

×

(lg1+Ign+lg2+lgm)

Conventional NV series (Type CA,
CS, SS produced prior to '91)
Rated sensitivity current:
I

n

10

×

{lg1+lgn+3

×

(lg2+lgm)}

lg1, lg2 : Leakage currents of cable

path during commercial
power supply operation

lgn*

: Leakage current of noise

filter on inverter input side

lgm

: Leakage current of motor

during commercial power
supply operation

0

20

40

60

80

100

120

2 3.5

8 1422 38 80

5.5

30 60100

150

1.5 3.7

2.2

7.5 1522

11

37

30

55

45

5.5

18.5

Cable size (mm )

2.0

1.0
0.7
0.5

0.3

0.2

0.1

Motor capacity (kW)

Example of leakage
current per 1km in cable
path during commercial
power supply operation
when the CV cable is
routed in metal conduit
(200V 60Hz)

L

eaka

ge cur

re

n

t (mA)

L

eaka

ge cur

re

n

t (mA)

2

Leakage current
example of 3-phase
induction motor
during commercial
power supply
operation
(200V 60Hz)

<Example>

NV

Ig1

Ign

Ig2

Igm

2mm ×5m

2mm ×70m

IM

3
200V
1.5kW
(2HP)

Inver-
ter

Noise

filter

2

2

(16.40feet)

(229.66feet)

CAUTION

The earth leakage circuit breaker should be installed to the primary (power

supply) side of the inverter.

In the connection neutral point grounded system, the sensitivity current

becomes worse for ground faults in the inverter secondary side. Hence, the
protective grounding of the load equipment should be 10

or less.

When the breaker is installed in the secondary side of the inverter, it may be

unnecessarily operated by harmonics if the effective value is less than the rating. In this
case, do not install the breaker since the eddy current and hysteresis loss increase and
the temperature rises.

* Note the leakage current value of the noise filter installed on the inverter input

side.

Progressive Super Series

(Type SP, CF, SF,CP)

Conventional NV

(Type CA, CS, SS)

5m (16.40feet)

Leakage current (Ig1) (mA)

20

×

1000m (3280.80feet)

= 0.10

Leakage current (Ign) (mA)

0 (without noise filter)

70m (229.66feet)

Leakage current (Ig2) (mA)

20

×

1000m (3280.80feet)

= 1.40

Motor leakage
current (Igm) (mA)

0.14

Total leakage current (mA)

1.66

4.78

Rated sensitivity current
(mA) (

≥≥≥≥

Ig

ЧЧЧЧ

10)

30

100