102

Parameter

Name

Factory

Setting

Setting

Range

Remarks

88

PID action
selection

20

20, 21

89

PID proportional
band

100%

0.1 to 999 %,

- - -

90

PID integral time

1s

0.1 to 999s,

- - -

91

PID upper limit

- - -

0 to 100%,

- - -

92

PID lower limit

- - -

0 to 100%,

- - -

93

PID action set
point for PU
operation

0%

0 to 100%

94

PID differential
time

- - -

0.01 to 10s,

- - -

Setting is enabled when Pr. 30 = "1"

<Setting>
(1) Basic PID control configuration

+-

IM

Kp: Proportion constant Ti: Integral time S: Operator Td: Differential time

Set point

Manipulated

variable

Motor

Feedback signal (Process value)

Inverter circuit :

Ti S

1

1+

+Td S

Kp

PID operation

Terminal 4

Pr. 93 or Treminal 2

(2) PID action overview

1) PI action

A combination of proportional control
action (P) and integral control action (I)
for providing a manipulated variable in
response to deviation and changes
with time.

REMARKS

PI action is the sum of P and I actions.

[Operation example for stepped
changes of process value]

Deviation Set point

Process value

Time

Time

Time

PI action

I action

P action