MITSUBISHI ELECTRIC FR-S520 User Manual

Page 23

Advertising
background image

14

3) FR-S520S-0.1K to 1.5K (-R)

FR-S520S-0.2K to 1.5K-EC (R)

Cables (mm

2

)

(*2)

Motor

Output

(kW

(HP))

Inverter

Model

Rated current of

Circuit Breaker

(Refer to

page 15)

(*1)

Magnetic

Contactor

(MC)

(Refer to

page 17)

Power

Factor

Improving

AC Reactor

(Refer to

page 18)

(*3)

Power

Factor

Improving

DC Reactor

(Refer to

page 18)

(*3)

R, S

<L

1

, N>

U, V, W

0.1

(1/8)

FR-S520S-
0.1K

30AF/5A

S-N10

FR-BAL-0.4K FR-BEL-0.4K

2

2

0.2

(1/4)

FR-S520S-
0.2K

30AF/10A

S-N10

FR-BAL-0.4K FR-BEL-0.4K

2

2

0.4

(1/2)

FR-S520S-
0.4K

30AF/10A

S-N20

FR-BAL-

0.75K

FR-BEL-

0.75K

2

2

0.75

(1)

FR-S520S-
0.75K

30AF/15A

S-N20

FR-BAL-1.5K FR-BEL-1.5K

2

2

1.5

(2)

FR-S520S-
1.5K

30AF/20A

S-N21

FR-BAL-2.2K FR-BEL-2.2K

2

2

4) FR-S510W-0.1K to 0.75K (-R)

FR-S510W-0.1K to 0.75K-NA

Cables (mm

2

)

(*2)

Motor

Output

(kW

(HP))

Inverter

Model

Rated current of

Circuit Breaker

(Refer to

page 15)

(*1)

Magnetic

Contactor

(MC)

(Refer to

page 17)

Power

Factor

Improving

AC Reactor

(Refer to

page 18)

(*3)

Power

Factor

Improving

DC Reactor

(Refer to

page 18)

(*4)

R, S

<L

1

, N>

U, V, W

0.1

(1/8)

FR-S510W-
0.1K

30AF/10A

S-N10

FR-BAL-

0.75K

−−

−−

−−

−−

2

2

0.2

(1/4)

FR-S510W-
0.2K

30AF/15A

S-N10

FR-BAL-1.5K

−−

−−

−−

−−

2

2

0.4

(1/2)

FR-S510W-
0.4K

30AF/20A

S-N20

FR-BAL-2.2K

−−

−−

−−

−−

2

2

0.75

(1)

FR-S510W-
0.75K

30AF/30A

S-N20

FR-BAL-3.7K

−−

−−

−−

−−

3.5

2

*1 For installations in the United States or Canada, the circuit breaker must be

inverse time or instantaneous trip type.

*2 The size of the cables assume that the wiring length is 20m (65.62feet).
*3 The power factor may be slightly less.
*4 The single-phase 100V power input model does not allow the power factor

improving DC reactor to be fitted.

Advertising