Setting – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 128

Advertising
background image

119

2

REMARKS

For computer link operation, set 65520 (HFFF0) as the value "888" and 65535

(HFFFF) as the value "- - -".

Refer to page 41 for handling the RS-485 connector.

Refer to the "parameter data code list" (page 177) for the data codes of the

parameters.

<Setting>

To make communication between the personal computer and inverter, the
communication specifications must be set to the inverter initially. If initial setting is not
made or there is a setting fault, data transfer cannot be made.
Note: After making the initial setting of the parameters, always reset the inverter. After

you have changed the communication-related parameters, communication
cannot be made unit the inverter is reset.

Parameter

Description

Setting

Description

n1

Communication
station number

0 to 31

Station number specified for communication from
the RS-485 connector.
Set the inverter station numbers when two or more
inverters are connected to one personal computer.

48

4800 bps

96

9600 bps

n2

Communication
speed

192

19200 bps

0

Stop bit length 1 bit

8 bits

1

Stop bit length 2 bits

10

Stop bit length 1 bit

n3

Stop bit length

7 bits

11

Stop bit length 2 bits

0

Absent

1

Odd parity present

n4

Parity check
presence/
absence

2

Even parity present

0 to 10

Set the permissible number of retries at occurrence
of a data receive error.
If the number of consecutive errors exceeds the
permissible value, the inverter will come to an
alarm stop (OPT).

n5

Number of
communication
retries

- - -

(65535)

If a communication error occurs, the inverter will
not come to an alarm stop. At this time, the inverter
can be coasted to a stop by MRS or RES input.
During a communication error (H0 to H5), the minor
fault signal (LF) is switched on. Allocate the used
terminal with any of Pr. 64, Pr. 65 (multi-function
outputs).

0

No communication

0.1 to 999

Set the communication check time [s] interval.
If a no-communication state persists for longer than
the permissible time, the inverter will come to an
alarm stop (OPT).

n6

Communication
check time
interval

- - -

Communication check suspension

0 to 150

Set the waiting time between data transmission to
the inverter and response.

n7

Wait time setting

- - -

Set with communication data.

0

Without CR

LF

1

With CR, without LF

n11

CR

LF

selection

2

With CR

LF