Display operation – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 85

Advertising
background image

76

Changing example

Changing the calibration parameter C4 "frequency setting

voltage gain" value

POINT

The calibration parameter C4 is an extended function parameter. Pr. 30 must be set to "1".

(2) Adjusting a deviation of the highest frequency from the Pr. 38

(Pr. 39) setting.
(2)-1) Making adjustment with a voltage applied directly across

terminals 2-5 (with a current flowing across terminals 4-5)

Confirm the RUN indication and operation
mode indication.
The inverter must be at a stop.
The inverter must be in the PU operation mode.
(Press the key)

1.

4.

5.

SET

2.

MODE

MODE

The parameter
number read
previously
appears.

6.

Press the key to show the analog
voltage analog-to-digital conversion value (%).

SET

SET

7.

Apply a 5V voltage.
(Turn the external potentiometer
connected to across terminals 2-5 to
the maximum (any position).)

1

2

3

4 5 6

7

8

9

10

Analog voltage
analog-to-digital
conversion value
(%) across
terminals 2-5

*

Press the key to choose the parameter

setting mode.

RUN

PU

EXT

*The value is nearly 100 (%) in the
maximum position of the potentiometer.

3.

Turn the setting dial to show " ".
Pr. 30 must be set to "1".
(For the Pr. 30 setting method, refer to
the instruction manual (basic).)

PU

EXT

Turn the setting dial until the calibration
parameter C4 "frequency setting
voltage gain" appears.

SET

Press the key to show " ".

Display

Operation

When adjusting Pr. 38

CAUTION

After performing operation in step 7, do not touch the setting dial

until completion of calibration.

Flicker ... Parameter setting complete!!

*The value is nearly 100 (%) in the
maximum position of the potentiometer.

8.

SET

(Adjustment complete)

*

SET

Press the key to set the value.

By turning the setting dial , you can read another parameter.

SET

Press the key to return to the indication (step 4).

SET

Press the key twice to show the next parameter ( ).

The frequency meter (indicator) connected to across terminals FM-SD (AM-

5)does not indicate just 50Hz ... Why?

The calibration parameter C1 "FM (AM) terminal calibration" value must

be set. (For the setting method, refer to the instruction manual (basic).)

When write is performed, an error (

) is displayed.

The gain and bias frequency settings are too close.