MITSUBISHI ELECTRIC FR-S520 User Manual

Page 161

Advertising
background image

152

3

Interval

Periodic*

Ar

e

a

o

f

In

spect

io

n

Inspection

Item

Description

D

a

ily

1 year

2 year

s

Method

Criterion

Instrument

Cont

ro

l c

irc

ui

t

Pr

ot

ec

ti

ve c

ir

c

ui

t

Operation
check

(1) Check

balance of
output
voltages
across
phases with
inverter
operated
independently.

(2) Perform

sequence
protective
operation
test to make
sure there is
no fault in
protective or
display
circuits.

(1) Measure

voltage
across
inverter
output
terminals U-
V-W.

(2) Simulate

connection of
inverter
protective
circuit output
terminals.

(1) Phase-to-

phase
voltage
balance
within 4V
(8V) for
200V
(400V).

(2) Fault must

occur
because of
sequence.

Digital
multimeter,
rectifier type
voltmeter

Cool

ing s

y

s

tem

Cooling
fan

(1) Check for

unusual
vibration and
noise.

(2) Check for

loose
connection.

(1) Turn by hand

with power
off.

(2) Visual check.

No unusual
vibration and
unusual noise.

Display

(1) Check for

LED lamp
blown.

(2) Clean.

(1) Lamps

indicate
indicator
lamps on
panel.

(2) Clean with

rag.

(1) Check that

lamps are
lit.

Di

s

p

la

y

Meter

Check that
reading is
normal.

Check reading of
meters on panel.

Must satisfy
specified and
management
values.

Voltmeter,
ammeter,
etc.

General

(1) Check for

unusual
vibration
and noise.

(2) Check for

unusual
odor.

(1) Auditory,

sensory,
visual
checks.

(2) Check for

unusual odor
due to
overheat,
damage, etc.

(1), (2) No fault.

Mot

o

r

Insulation
resistance

(1) Check with

megger
(across
terminals
and ground
terminal).

(1) Disconnect

cables from
U, V, W
(including
motor cables).

5M

or more.

500V
megger

Note: The value for the 400V class is indicated in the parentheses.

* For periodic inspection, contact you nearest Mitsubishi sales representative.