158

3

Measuring Points and Instruments

Item

Measuring Point

Measuring

Instrument

Remarks

(Reference Measured Value)

Power supply
voltage
(V1)

Across R-S, S-T
and T-R

Moving-iron type
AC voltmeter

Is the commercial power supply
within permissible variation of AC
voltage
(Refer to page 161)

Power supply side
current
(I1)

R, S and T line
currents

Moving-iron type
AC ammeter

Power supply side
power
(P1)

At R, S and T, and
across R-S, S-T
and T-R

Electrodynamic
type single-phase
wattmeter

P1 = W11 + W12 + W13
(3-wattmeter method)

Power supply side
power factor
(Pf1)

Calculate after measuring power supply voltage, power supply side current
and power supply side power.
[For three-phase power supply]

[For single-phase power supply]

Pf1=

P1

3V1 I1

100%

Pf1=

P1

V1 I1

100%

Output side voltage
(V2)

Across U-V, V-W
and W-U

Rectifier type AC
voltmeter (Note 1)
(Cannot be
measured by
moving-iron type)

Difference between phases is
within

±

1% of maximum output

voltage.

Output side current
(I2)

U, V and W line
currents

Moving-iron type
AC ammeter
(Note 2)

Current should be equal to or
less than rated inverter current.
Difference between phases is
10% or lower.

Output side power
(P2)

At U, V and W, and
across U-V and V-
W

Electrodynamic
type single-phase
wattmeter

P2 = W21 + W22
2-wattmeter method (or 3-
wattmeter method)

Output side power
factor
(Pf2)

Calculate in similar manner to power supply side power factor.

Pf2=

P2

3V2 I2

100%

Converter output

Across P-N

Moving-coil type
(such as a meter)

Inverter LED display is lit.
1.35 × V1

Across 2 (+)-5

0 to 5V/0 to 10VDC

Frequency setting
signal

Across 4 (+)-5

Moving-coil type
(Meter, etc. may be
used)
(Internal resistance:
50k

or larger)

4 to 20mADC

"5" i

s

c

o

mmon.