1) pu operation interlock – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 109

Advertising
background image

100

(1) PU operation interlock

PU operation interlock forces the operation mode to be changed to the external
operation mode when the MRS signal switches off. This function prevents the inverter
from being inoperative by the external command if the mode is accidentally left
unswitched from the PU operation mode.

1) Preparation

Set "7" in Pr. 79 (operation mode selection).
Set the terminal used for MRS signal input with any of Pr. 60 to Pr. 63 (input terminal

function selection).
Refer to page 88 for Pr. 60 to Pr. 63 (input terminal function selection).

REMARKS

When terminal assignment is changed using Pr. 60 to Pr. 63, the other functions
may be affected.
Check the functions of the corresponding terminals before making settings.

2) Function

MRS Signal

Function/Operation

ON

Output stopped during external operation.
Operation mode can be switched to PU operation mode.
Parameter values can be rewritten in PU operation mode.
PU operation allowed.

OFF

Forcibly switched to external operation mode.
External operation allowed.
Switching to PU operation mode inhibited.

<Function/operation changed by switching on-off the MRS signal>

Operating Condition

Operation

mode

Status

MRS

Signal

Operation

Mode

(*2)

Operating Status

Parameter

Write

Switching to

PU Operation

Mode

During

stop

ON

OFF

(*1)

During stop

Allowed

disallowed

Disallowed

PU

During

operation

ON

OFF

(*1)

PU

External

If external operation
frequency setting
and start signal are
entered, operation is
performed in that
status.

Allowed

disallowed

Disallowed

OFF

ON

Disallowed

disallowed

Allowed

During

stop

ON

OFF

During stop

Disallowed

disallowed

Disallowed

OFF

ON

During operation

output stop

Disallowed

disallowed

Disallowed

External

During

operation

ON

OFF

External

Output stop

operation

Disallowed

disallowed

Disallowed