.10 Operation Selection Function Parameters

2

.10.1

Retry function

When any protective function (major fault) is activated and the inverter stops its
output, the inverter itself resets automatically and performs retries. You can
select whether retry is made or not, alarms reset for retry, number of retries
made, and waiting time.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

66

Retry selection

0

0 to 3

67

Number of
retries at alarm
occurrence

0

0, 1 to

10, 101

to 110

68

Retry waiting
time

1s

0.1 to

360s

69

Retry count
display erase

0

0

Setting is enabled when Pr. 30 = "1"

<Setting>

Use Pr. 66 to choose the protective functions (major failures) for retries.

Protective Functions (Major Failures) for Retries

Pr. 66 Setting

OCT OVT THM THT

FIN

GF

OHT OLT

PE

PUE RET CPU OPT

0
1
2
3

* Indicates the retry items selected. (OCT denotes any of OC1 to OC3 and OVT

any of OV1 to OV3.)

Use Pr. 67 to set the number of retries at alarm occurrence.

Pr. 67 Setting

Number of Retries

Alarm Signal Output

0

Retry is not made.

———

1 to 10

1 to 10 times

Not output every time *

101 to 110

1 to 10 times

Output every time

* If the retry count is exceeded, "

" (retry count excess) is displayed.

Use Pr. 68 to set the waiting time from when an inverter alarm occurs until a restart
in the range 0.1 to 360s.
Reading the Pr. 69 value provides the cumulative number of successful restart times
made by retry. The setting of "0" erases the cumulative number of times.