5 input filter time constant [p74, 6 reset selection/pu stop selection [p75, 5 input filter time constant – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 103: 6 reset selection/pu stop selection, Setting

Advertising
background image

94

2

.10.5

Input filter time constant

You can set the input section's built-in filter constant for an external voltage or
current frequency setting signal.

Effective for eliminating noise in the frequency setting circuit.

Parameter

Name

Factory Setting

Setting Range

Remarks

74

Input filter time
constant

1

0 to 8

Setting is enabled when
Pr. 30 = "1"

REMARKS

Increase the filter time constant if steady operation cannot be performed due to
noise. A larger setting results in slower response. (The time constant can be set
between approximately 1ms to 1s with the setting of 0 to 8. A larger setting results
in a larger filter time constant.)

2

.10.6

Reset selection/PU stop selection

You can make reset input acceptance selection and choose the stop function
from the operation panel (PU).

Reset selection

: You can choose the reset function input (RES signal)

timing.

PU stop selection: When an alarm etc. occurs in any operation mode, you can

make a stop from the operation panel by pressing the

STOP

RESET

key.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

75

Reset selection/
PU stop selection

14

0, 1,

14, 15

Setting is enabled when Pr. 30 = "1"

<Setting>

Pr. 75

Setting

Reset Selection

PU Stop Selection

0

Reset input normally enabled.

1

Enabled only when the protective
function is activated.

The PU stop key is invalid. Note that the

STOP

RESET

key is valid only in the PU operation mode or

combined operation mode (Pr. 79 = "4").

14

Reset input normally enabled.

15

Enabled only when the protective
function is activated.

Pressing the

STOP

RESET

key decelerates the

inverter to a stop in any of the PU, external and

communication operation modes.