1 japanese version, 1 terminal connection diagram, Inverter – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 11

Advertising
background image

2

1

.1 Japanese Version

1

.1.1 Terminal connection diagram

FR-S520-0.1K to 3.7K (-R) (-C)
FR-S540-0.4K to 3.7K (-R)

Power factor improving
DC reactor
(FR-BEL: Option)

PC

External transistor common

24VDC power supply

Contact input common (source)

STF

STR

RH

RM

RL

SD

Forward rotation start

Reverse rotation start

Middle

High

Low

Frequency setting signals (Analog)

10 (+5V)

2

2

3

1

4 to 20mADC (+)

4 (4 to 20mADC)

Frequency
setting
potentiometer
1/2W1k
(*4)

SE

Running

FM

SD

Control input signals
(No voltage input allowed)

Jumper: Remove this
jumper when FR-BEL
is connected.

Motor

IM

Ground

Alarm
output

U

V

W

P1

P

N

(+)

(-)

Earth (Ground)

Selected

Multi-speed selection

Operation status
output

Contact input common

5 (Common)

Open collector
output common

Current input (-)

3-phase AC
power supply

NFB

R

S

T

MC

Open
collector
outputs

Calibration
resistor (*2)

SINK

SOURCE

RS-485 Connector (*1)

Inverter

Main circuit terminal

Control circuit input terminal

Control circuit output terminal

DC 0 to 5V
DC 0 to 10V

Indicator
1mA full-scale
Analog meter
(Digital indicator)

1mA

(*3)

When using the current input as
the frequency setting signal, set
"4" in any of Pr. 60 to Pr. 63 (input
terminal function selection), assign
AU (current input selection) to any
of terminals RH, RM, RL and STR,
and turn on the AU signal.

(Note)

Be careful not to short
terminals PC-SD.

*5

*5

*5

*5

RUN

*6

C

*6

B

*6

A

*6

REMARKS

*1 Only the type with RS-485 communication function.
*2 Not needed when the setting dial is used for calibration. This resistor is used

when calibration must be made near the frequency meter for such a reason as a
remote frequency meter. Note that the needle of the frequency meter may not
deflect to full-scale when the calibration resistor is connected. In this case, use
both the resistor and setting dial for calibration.

*3 You can switch between the sink and source logic positions. Refer to page 25.
*4 When the setting potentiometer is used frequently, use a 2W1k

potentiometer.

*5 The terminal functions change with input terminal function selection (Pr. 60 to

Pr. 63). (Refer to page 38, 88) (RES, RL, RM, RH, RT, AU, STOP, MRS, OH,
REX, JOG, X14, X16, (STR) signal selection)

*6 The terminal functions change with output terminal function selection (Pr. 64,

Pr. 65). (Refer to page 90) (RUN, SU, OL, FU, RY, Y12, Y13, FDN, FUP, RL,
LF, ABC signal selection)