.11 Auxiliary Function Parameters

2

.11.1

Slip compensation

The inverter output current may be used to assume motor slip to keep the motor
speed constant.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

95

Rated motor slip

- - -

0 to 50%,

- - -

96

Slip compensation time
constant

0.5s

0.01 to 10s

97

Constant-output region slip
compensation selection

- - -

0, - - -

Setting is enabled when
Pr. 30 = "1"

<Setting>

Synchronous speed at base frequency - rated speed

Rated slip =

Synchronous speed at base frequency

×100[%]

Parameter

Setting

Function

0.01 to 50%

Used to set the rated motor slip.

95

0, - - -

Slip compensation is not made.

96

0.01 to 10s

Used to set the slip compensation response time. (*)

0

Slip compensation is not made in the constant output
range (frequency range above the frequency set in Pr. 3).

97

- - -

Slip compensation is made in the constant output range.

* When this value is made smaller, response will be faster.

However, as load inertia is greater, a regenerative overvoltage (OVT) error is
more liable to occur.

REMARKS

When making slip compensation at 60Hz<50Hz>, set the maximum frequency to
slightly higher than 60Hz<50Hz>.
In the factory setting status, it is clamped at 60Hz<50Hz>.

2

.11.2

Automatic torque boost selection

You can choose automatic torque boost control.

Automatic torque boost control
Not only gives the motor the optimum excitation but also provides high torque
even in a low speed range.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

98

Automatic torque boost
selection (motor capacity)

- - -

0.1 to 3.7kW,

- - -

Setting is enabled when
Pr. 30 = "1"