1) operational functions – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 125

Advertising
background image

116

2

.14 Communication Parameters (Only for the type having

the RS-485 communication function)

You can perform communication operation from the RS-485 connector of the
inverter through RS-485.

(1) Operational functions

1) Operation mode switching
[Operation mode switching method]

Computer

link

operation

Switching by

computer

program

External

operation

PU

operation

Switching by operation

panel/parameter

unit (FR-PU04)

(Switching must
not be made)

C

D

E

F

B

A

Symbol

Switching Type

Switching Method

A

PU operation to external
operation

Using the

PU

EXT

key of the operation panel or

PU

/

EXT

key of the parameter unit (FR-PU04)

B

External operation to PU
operation

Using the

PU

EXT

key of the operation panel or

PU

/

EXT

key of the parameter unit (FR-PU04)

C

External operation to
computer link operation

Using the
computer program

D

Computer link operation to
external operation

Using the
computer program

Read (H7B)/
Write (HFB)

H0000:
Communication
operation
H0001: External
operation

E

PU operation to computer
link operation

Switching must not be made
(External operation may be selected at

A

and then

switched to computer link operation at

C

*)

F

Computer link operation to
PU operation

Switching must not be made
(External operation may be selected at

D

and then

switched to PU operation at

B

*)

* When "1" is set in the communication parameter n10 "link start mode selection",

the inverter is placed in the computer link operation mode at power-on or inverter
reset. (Note that it is overridden by the Pr. 79 "operation mode selection" setting.)

REMARKS

Unlike the other inverters, the FR-S500 series is not the type of inverter whose
operation panel is removed to make communication.
When the setup software is used to switch to the PU operation mode (Pr. 79 = 1, 3,

4), parameter setting cannot be made. At that time, pressing the

RUN

key of the

operation panel starts the inverter.

Advertising