2 layout and wiring of main circuit terminals – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 14

Advertising
background image

5

1

NOTE

To prevent a malfunction due to noise, keep the signal cables more than 10cm
(3.94inches) away from the power cables.

FR-S510W-0.1K to 0.75K-NA

Power supply

NFB

R

S

Motor

IM

Earth
(Ground)

U

V

W

MC

REMARKS

To ensure safety, connect the power input to the inverter via a magnetic contactor

and earth leakage circuit breaker or no-fuse breaker, and use the magnetic
contactor to switch power on-off.

The output is three-phase 200V.

1

.2.2 Layout and wiring of main circuit terminals

FR-S520-0.1K, 0.2K, 0.4K, 0.75K-NA

FR-S520-1.5K, 2.2K, 3.7K-NA
FR-S540-0.4K, 0.75K, 1.5K, 2.2K, 3.7K-NA (R)

P1

U

V

W

IM

R

S

T

N

P

Jumper

Power

supply

Motor

P1

Jumper

R

S

T

U

V

W

IM

N

P

Power

supply

Motor

FR-S510W-0.1K, 0.2K, 0.4K-NA

FR-S510W-0.75K-NA

U

V

W

IM

N

P

R

S

Power

supply

Motor

U

V

W

IM

N

P

R

S

Power
supply

Motor

CAUTION

The power supply cables must be connected to R, S, T. If they are connected to

U, V, W, the inverter will be damaged. (Phase sequence need not be matched.)

Connect the motor to U, V, W.

Turning on the forward rotation switch (signal) at this time rotates the motor
counterclockwise when viewed from the load shaft.