132

<Setting>

n10

Setting

Pr. 79

Operation Mode

Mode at Power-On or at Power Restoration

after Instantaneous Power Failure

0

PU or external operation Placed in the external operation mode.

1

PU operation

Placed in the PU operation mode.

2

External operation

Placed in the external operation mode.

3

External/PU combined
operation mode

The running frequency is given in the PU
operation mode and the start signal in the
external operation mode.

4

External/PU combined
operation mode

The running frequency is given in the external
operation mode and the start signal in the PU
operation mode.

7

External operation mode

MRS signal ON .....Can be switched to PU

operation mode.
(Output stop during
external operation)

MRS signal OFF ...Switching to PU operation

mode inhibited.

0

(Factory

setting)

8

External/PU combined
operation mode

X16 signal ON .......Switched to external

operation mode.

X16 signal OFF .....Switched to PU operation

mode.

0

Computer link operation

Disabled when PU is selected. Enabled when
external is selected.

1

PU operation only

Disabled

2

Computer link operation

Enabled

3

External/PU combined
operation

Disabled

4

External/PU combined
operation

Disabled

7

External operation (PU
operation interlock)

Enabled only for external operation when the
PU interlock signal (MRS) is ON.

1

8

PU or external (signal
switching)

Enabled only for external operation (X16: ON).

n10 can be changed independently of the operation mode of the operation panel.
Setting of n10 = "1" is made valid when "0" or "2" is set in Pr. 79 "operation mode
selection".

Refer to

to

(page 118)

2

.14.4

E

2

PROM write selection

You can choose whether the parameters are stored into E

2

PROM or not at the

parameter setting for computer communication.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

n12 (342)

E

2

PROM write

selection

0

0, 1

0: Written to RAM and E

2

PROM

1: Written to RAM only

Not written to E

2

PROM*

Setting is enabled when Pr. 30 = "1"

The parameter number in parentheses is the one for use of the parameter unit (FR-PU04).
* When reset is performed, the parameter value will be the value of E

2

PROM.