5 pu disconnection detection/pu setting lock [n17, Caution, 5 pu disconnection detection/pu setting lock – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 144

Advertising
background image

135

2

2

.15.5

PU disconnection detection/PU setting lock

You can choose the connector disconnection detection function of the parameter
unit (FR-PU04) and the operation write of the parameter unit (FR-PU04).

PU disconnection detection : This function detects that the parameter unit

(FR-PU04) has been disconnected from the
inverter for longer than 1 second and causes
the inverter to provide an alarm output (PUE)
and come to an alarm stop. When the PU has
been disconnected since before power-on, it is
not judged as an alarm.

PU operation

: Operation performed to perform running,

frequency setting or parameter setting from the
parameter unit (FR-PU04).

Parameter

Name

Factory

Setting

Setting

Range

Remarks

n17 (993)

PU disconnection
detection/PU setting lock

0

0, 1, 10

Setting is enabled when
Pr. 30 = "1"

<Setting>

n17 Setting

PU Disconnection Detection

PU Setting Lock

0

Operation is continued as-is if the PU is
disconnected (without PU disconnection detection)

1

Inverter output is shut off when the PU is
disconnected (with PU disconnection detection)

PU operation valid

10

Operation is continued as-is if the PU is
disconnected (without PU disconnection detection)

PU operation invalid*

* The monitor display and

STOP

RESET

key are valid.

REMARKS

When RS-485 communication operation is performed through the RS-485
connector, the reset selection/PU stop selection function is valid but the PU
disconnection detection function is invalid.

CAUTION

Do not reset the inverter while the start signal is being input.

Doing so will cause the inverter to start immediately after a reset, leading to
hazardous conditions.