.3.4 Insulation resistance test using megger

1) Before performing the insulation resistance test using a megger on the external

circuit, disconnect the cables from all terminals of the inverter so that the test
voltage is not applied to the inverter.

2) For the continuity test of the control circuit, use a meter (high resistance range) and

do not use the megger or buzzer.

3) For the inverter, conduct the insulation resistance test on the main circuit only as

shown below and do not perform the test on the control circuit. (Use a 500VDC
megger.)

R

S

T

U

V

W

Inverter

Earth terminal

500VDC

megger

Power supply

IM

Motor

3

.3.5 Pressure test

Do not conduct a pressure test. The inverter may be deteriorated.

3

.3.6 Daily and periodic inspection

Interval

Periodic*

Ar

e

a

o

f

In

spect

io

n

Inspection

Item

Description

D

a

ily

1 year

2 year

s

Method

Criterion

Instrument

Surrounding
environment

Check ambient
temperature,
humidity, dust,
dirt, etc.

Make
measurement
5cm (1.97inches)
away from
inverter.

Ambient
temperature:
-10ºC to +50ºC
(14ºF to 122ºF),
non-freezing.
Ambient
humidity: 90%
or less, non-
condensing.

Thermo-
meter,
hygrometer,
recorder

Overall unit

Check for
unusual
vibration and
noise.

Visual and
auditory checks.

No fault.

Gener

al

Power
supply
voltage

Check that main
circuit voltage is
normal.

Measure voltage
across inverter
terminals R-S-T

Within
permissible AC
(DC) voltage
fluctuation
(Refer to page
161)

Meter, digital
multimeter